Supply and exhaust ventilation unit with heat recovery, capacity up to 600 m3 / h, in an insulated housing. Efficiency of recuperation up to 65%.
The unit is equipped with EC motors to reduce power consumption from 1.5 to 3 times while maintaining high efficiency and optimal control over the whole speed spectrum. An unquestionable advantage of the EC engine is its high KPD (reaches 90%).
The filters have class G4 (extract air) and F7 (air supply) filters.
Type | Efficiency [m3/h] | Max. fan power [W] | Max. temp. [°C] |
VUT 300-1 H EC | 300 | 2×70 | -25/+60 |
VUT 300-2 H EC | 300 | 2×70 | -25/+60 |
VUT 400 H EC | 400 | 2×175 | -25/+60 |
VUT 600 H EC | 600 | 2×175 | -25/+60 |
Type | Sizes [mm] | |||||||||
ØD | B | B1 | B2 | B3 | H | H1 | H2 | L | L1 | |
VUT 300-1 H EC | 149 | 420 | 390 | 100 | 159 | 562 | 215 | 147 | 829 | 876 |
VUT 300-2 H EC | 159 | 420 | 390 | 100 | 159 | 562 | 215 | 147 | 829 | 876 |
VUT 400 H EC | 199 | 420 | 390 | 100 | 159 | 562 | 215 | 147 | 829 | 876 |
VUT 600 H EC | 199 | 420 | 390 | 100 | 159 | 562 | 215 | 147 | 829 | 876 |